Comprehensive ISA-101 design rules for Human Machine Interfaces in process automation, with detailed reference files covering color design, display hierarchy, navigation, alarms, human factors, performance, and lifecycle management. Use when designing, building, reviewing, or generating code for HMIs, control system displays, SCADA screens, or industrial control panels and comprehensive ISA-101 coverage is needed. Use when deep-diving into alarm design, color standards, navigation patterns, human factors, performance requirements, or HMI lifecycle management.

references/display-hierarchy-and-styles.md

View on GitHub
# HMI Display Hierarchy & Styles — Agent Instructions

When designing HMI display systems, structure displays in a 4-level hierarchy and select the appropriate display style for each.

## The 4-Level Display Hierarchy

### Level 1 — Overview / Dashboard
**Purpose:** Continuous awareness of the entire span of control

**Requirements:**
- Single display showing ALL key parameters for operator's full scope
- May span multiple monitors if all are simultaneously visible
- Continuously displayed (dedicated monitor when possible)

**Must Include:**
- Key process parameters with actual values
- Abnormal status with deviation severity and direction of change
- All top-priority alarms, positioned near associated equipment
- Embedded sparkline/mini trends on critical variables
- Status of related utilities, upstream/downstream areas
- Cost/performance KPIs if relevant

**Must NOT Include:**
- Control actions (no setpoint changes from Level 1)
- Excessive detail — this display must be scannable in seconds

**Design Pattern:**
```
┌─────────────────────────────────────────────────────┐
│                  PLANT OVERVIEW                      │
├──────────┬──────────┬──────────┬─────────────────────┤
│ Area A   │ Area B   │ Area C   │ Utilities / KPIs    │
│          │          │          │                     │
│ Key val  │ Key val  │ Key val  │ Cost $/hr           │
│ ~trend~  │ ~trend~  │ ~trend~  │ Key deviations      │
│ Alarm?   │ Alarm?   │ Alarm?   │ Upstream/downstream │
│ Status   │ Status   │ Status   │                     │
└──────────┴──────────┴──────────┴─────────────────────┘
```

### Level 2 — Unit/Area Operating Displays
**Purpose:** Primary working displays for routine monitoring and control

**Requirements:**
- One major system or subsystem per display
- Contains ALL controllers and indicators for routine operations
- Task-based: operator handles most work here with minimal navigation
- Includes start-up/shutdown task-specific views

**Must Include:**
- All high and medium priority alarms for the area
- Clear navigation cues for non-displayed low priority alarms
- Primary controllers for the process area
- Enough information to control under most normal conditions

**Design Pattern:**
```
┌─────────────────────────────────────────────────────┐
│              BOILER HOUSE OPERATIONS                 │
├────────────┬────────────┬────────────┬───────────────┤
│ Boiler 1   │ Boiler 2   │ Boiler 3   │ Common        │
│ Status:ON  │ Status:ON  │ Status:OFF │ Systems       │
│ [Fuel Gas] │ [Fuel Gas] │ [Fuel Gas] │               │
│ [O2]       │ [O2]       │ [O2]       │ [Steam Hdr P] │
│ [Steam F]  │ [Steam F]  │ [Steam F]  │ [BFW]         │
│ [Drum L]   │ [Drum L]   │ [Drum L]   │ [Cost $/hr]   │
│ Controllers│ Controllers│ Controllers│               │
└────────────┴────────────┴────────────┴───────────────┘
```

### Level 3 — Detail / Troubleshooting Displays
**Purpose:** Detailed views for non-routine operations and diagnostics

**Requirements:**
- P&ID-style or schematic detail of specific equipment
- All control loops, indicators, and interlocks
- Used for lineup changes, equipment switching, diagnostics
- Task-based: support troubleshooting workflows

**Must Include:**
- All alarm priorities for depicted equipment
- Interlock and permissive status
- Detailed equipment state information

### Level 4 — Diagnostic / Reference Displays
**Purpose:** Deepest detail level for point data, procedures, help

**Characteristics:**
- Operating procedures for individual equipment
- Help information for equipment control and diagnostics
- Detailed safety shutdown information
- Interlock and permissive logic details
- Often displayed as popups or faceplates (not full-screen)
- Not primarily for control, but control access may exist

---

## Display Styles

Select the most effective style based on functional requirements and data characteristics.

### Process Display (P&ID / PFD Style)
**Use for:** Showing equipment, piping, and instrumentation relationships
- Graphic representation of process equipment
- Shows physical flow and connections
- Most common style for Level 2 and Level 3 displays
- Equipment symbols should follow standard ISA symbology

### Functional Overview / Dashboard
**Use for:** KPIs, cross-area performance summaries
- Representation of functional relationships between data
- Sparklines, bar charts, gauges, digital readouts
- Best for Level 1 displays
- Focus on trends and deviations, not raw numbers

### Schematic Overview
**Use for:** Operator's span of control at a glance
- Informational overview of the entire area
- Simplified equipment representation
- Good for Level 1 and high-level Level 2

### List / Table
**Use for:** Tabular data that doesn't benefit from graphical representation
- Equipment lists, calibration tables, parameter tables
- Rows of text and numeric data
- May include small equipment symbols inline

### Trend / Graph
**Use for:** Showing data evolution over time
- Real-time or historical data charts
- Statistical process control charts
- Include reference lines for normal/alarm ranges
- Time axis should match process dynamics

### Group (Faceplate Array)
**Use for:** Monitoring multiple similar controllers side-by-side
- Array of standardized controller faceplates
- Each shows SP, PV, OP, mode, bar graph
- Great for comparing parallel equipment (all flow valves, all temperature loops)

### Topology / Location
**Use for:** Physical or logical system layout
- Network diagrams, electrical one-line diagrams
- Fire detection zone maps
- Physical building/plant layouts with status indicators

### Logic Monitor
**Use for:** Visualizing control logic
- Boolean / function block diagrams
- Ladder logic displays
- Sequence diagrams
- Show live state of inputs/outputs

### Procedural
**Use for:** Step-by-step operational sequences
- Sequential function charts
- Procedure checklists with electronic signatures
- Trip check procedures
- Show current step, completed steps, remaining steps

### Health / Diagnostic
**Use for:** System infrastructure monitoring
- Network health, server status, controller status
- Communication path monitoring
- Battery/UPS status

### Alarm List
**Use for:** Alarm management
- Active alarm summary (sortable by priority, time, area)
- Shelved alarm list
- Out-of-service alarm list
- Event/message logs

### Video
**Use for:** Live or recorded process monitoring
- CCTV feeds
- Process cameras
- Security monitoring

---

## Navigation Between Levels

```
Level 1 (Overview) ←→ Level 2 (Operating)
        ↕                     ↕
                        Level 3 (Detail)
                              ↕
                        Level 4 (Diagnostic)
```

- Drill DOWN: click on area/equipment to see more detail
- Drill UP: always provide a "back to overview" path
- Lateral: navigate between peer systems at the same level
- Yoking: clicking an item can simultaneously update multiple screens/panels

### Click Budget:
| Destination | Max Clicks |
|-------------|-----------|
| Any critical display | 1-2 |
| Any non-critical display | 3 |
| Alarm summary | 1 (always) |
| System diagnostics | 1-2 |
finishing-a-development-branchobra/superpowersUse when implementation is complete, all tests pass, and you need to decide how to integrate the workStars: 322kUpdated Claude CodeCodexVerifiedInstall
systematic-debuggingobra/superpowersUse when encountering any bug, test failure, or unexpected behavior, before proposing fixesStars: 322kUpdated Claude CodeCodexVerifiedInstall
test-driven-developmentobra/superpowersUse when implementing any feature or bugfix, before writing implementation codeStars: 322kUpdated Claude CodeCodexVerifiedInstall
skill-creatoranthropics/skillsCreate new skills, modify and improve existing skills, and measure skill performance. Use when users want to create a skill from scratch, edit, or optimize an existing skill, run evals to test a skill, benchmark skill performance with variance analysis, or optimize a skill's description for better triggering accuracy.Stars: 198kUpdated Claude CodeCodexVerifiedInstall