VerifiedBuild industrial-grade SCADA/HMI dashboards in MATLAB following industrial-HMI conventions (ISA-101-aligned): gray-field philosophy, alarms at source, write safeguards, fixed-range trends, drill-down layout. Produces a real App Designer app (.mlapp, or plain-text .m+.xml on R2026b+) by handing serialization to the matlab-build-app skill when available, and falls back to a programmatic .m app otherwise. Use when wrapping OPC UA / Modbus / MQTT / OSI PI / PI AF monitoring scripts into a live operator app, building plant overviews, designing operator dashboards, or any time a user asks for a "SCADA dashboard", "HMI", "plant dashboard", "operator screen", or "industrial monitoring app" in MATLAB. Trigger on: SCADA, HMI, industrial dashboard, plant overview, operator screen, uigauge, uilamp, alarm banner, gray-field, ISA-101, OPC UA dashboard, setpoint, write safeguards, alarm visualization, OSIsoft PI, AVEVA PI, PI Server, PI Data Archive, PI AF, PI Asset Framework, piclient, afclient.
| File | Kind | Size |
|---|---|---|
| SKILL.md | skill md | 21.6 KB |
| assets/design-report-schema.json | config | 9.9 KB |
| assets/designReportReadback.m | other | 12.5 KB |
| assets/hmi-spec-template.md | markdown | 18.4 KB |
| manifest.yaml | config | 1.7 KB |
| references/alarm-patterns.md | markdown | 10.9 KB |
| references/app-designer-gotchas.md | markdown | 9.0 KB |
| references/app-designer-handoff.md | markdown | 17.7 KB |
| references/color-and-layout-rules.md | markdown | 16.3 KB |
| references/common-mistakes.md | markdown | 49.6 KB |
| references/key-functions.md | markdown | 4.1 KB |
| references/known-schema-patterns.md | markdown | 4.1 KB |
| references/pi-af-cheatsheet.md | markdown | 16.7 KB |
| references/protocol-cheatsheet.md | markdown | 19.1 KB |
| references/server-agnostic-discovery.md | markdown | 8.4 KB |
| references/trend-config-reference.md | markdown | 10.9 KB |
| references/widget-selection-flowchart.md | markdown | 6.6 KB |
| references/write-safeguards-reference.md | markdown | 9.2 KB |
references/alarm-patterns.md
View on GitHub# Alarm Patterns
Alarms in an industrial HMI are a **state applied to existing widgets**, not a popup or a separate alarm widget. Every alarm is shown in three places at once: at the source, in a persistent banner, and (on the detail screen) in a list.
## The three required surfaces
1. **At source.** The widget showing the alarming node changes color (gauge `ScaleColors` band, table row background, lamp color, trend trace highlight).
2. **Persistent banner.** A top-row `uilabel` that lists active alarms across the whole HMI, color-coded by highest active severity.
3. **Alarm list (detail screen).** A `uitable` with columns Timestamp, Node, Severity, Value, State (Active/Acknowledged/Cleared).
If any of the three is missing, the alarm is unsafe. Operators on a different screen will not see a source annotation; operators on the source screen will not see siblings; nobody can audit cleared alarms without a list.
## Severity levels
Use exactly three:
| Severity | Color | When |
|----------|-------|------|
| Critical | Red `[0.85 0 0]` | Safety limit exceeded; immediate operator action required |
| Warning | Amber `[1 0.7 0]` | Approaching limit; pre-trip; advisory action |
| Advisory | Blue `[0.4 0.6 1.0]` | Informational; data quality; non-process |
Audible/visual flash is for **Critical only**. Flashing on warnings desensitizes operators.
## Threshold rules
```
IF value >= high_critical (HH) → Critical (red)
IF value >= high_warning (H) → Warning (amber)
IF value <= low_warning (L) → Warning (amber)
IF value <= low_critical (LL) → Critical (red)
ELSE → Normal (gray-field)
```
## Pattern A — Gauge `ScaleColors` keyed to LL/L/H/HH
> **Set `Limits` before the bands, and make it cover them.** `ScaleColors`/`ScaleColorLimits` work on all four gauge styles (`'linear'`, `'semicircular'`, `'circular'`, `'ninetydegree'`), but only the part of a band inside `Limits` is drawn — a band outside it is silently clipped (no error, no color). Set `Limits` to the node's spec range so every LL/L/H/HH band lies inside it. See `references/common-mistakes.md` entry 23.
The most important pattern: encode the alarm thresholds **at construction**, so the alarm state is visible in the gauge itself with no runtime logic. The agent does not need to recompute "is this alarm" on every update — the gauge does it visually.
> **Common Mistake — green for "normal".** LLMs default to green for the OK band because of "green = good" priors. ISA-101 forbids it: green is reserved for *operator-verified-OK* states (rare; explicit). The normal band MUST be neutral gray `[0.5 0.5 0.5]`. Using `[0 1 0]`, `[0 0.6 0]`, or `'green'` in `ScaleColors` is a violation. See `references/common-mistakes.md` entry 8.
```matlab
g = uigauge(parent, 'linear', 'Limits', [0 250]);
% Five bands. Order matches ScaleColorLimits rows (low→high).
g.ScaleColors = [0.85 0 0; % LL (0–40): Critical red
1 0.7 0; % L (40–60): Warning amber
0.5 0.5 0.5; % normal (60–200): gray-field
1 0.7 0; % H (200–230): Warning amber
0.85 0 0]; % HH (230–250): Critical red
g.ScaleColorLimits = [0 40;
40 60;
60 200;
200 230;
230 250];
```
### Three-band fallback — single-sided alarms
Many nodes only have an upper alarm (temperatures that should never overheat) or only a lower alarm (pass-rates that should never drop). Use 3 bands: `normal/H/HH` or `LL/L/normal`. The shape of `ScaleColors` and `ScaleColorLimits` adjusts:
```matlab
% Upper-only alarm — e.g., WeldingRobot1_Temperature with warn=90, alarm=100
g = uigauge(parent, 'linear', 'Limits', [0 150]);
g.ScaleColors = [0.5 0.5 0.5; % normal: gray (0–90)
1 0.7 0; % H: amber (90–100)
0.85 0 0]; % HH: red (100–150)
g.ScaleColorLimits = [0 90;
90 100;
100 150];
% Lower-only alarm — e.g., PassRate with warn=85, alarm=70
g = uigauge(parent, 'linear', 'Limits', [0 100]);
g.ScaleColors = [0.85 0 0; % LL: red (0–70)
1 0.7 0; % L: amber (70–85)
0.5 0.5 0.5]; % normal: gray (85–100)
g.ScaleColorLimits = [0 70;
70 85;
85 100];
```
The general rule: drop bands whose width would be zero. Five-band 5-band `[LL,L,normal,H,HH]` is the maximum; degrade to 3-band when one side has no alarm threshold.
## Pattern B — Persistent alarm banner
Reserve row 1 of the top-level grid for the banner. It is part of the gray-field background when no alarms are active.
```matlab
gl = uigridlayout(fig, [3 1]);
gl.RowHeight = {28, '1x', '1x'};
gl.BackgroundColor = [0.78 0.78 0.78];
banner = uilabel(gl, ...
'Text', 'No active alarms', ...
'BackgroundColor', [0.86 0.86 0.86], ...
'FontWeight', 'bold', ...
'FontColor', [0.2 0.2 0.2], ...
'HorizontalAlignment', 'center');
banner.Layout.Row = 1;
```
Update logic (called from the data callback whenever an alarm state changes):
```matlab
function refreshBanner(app)
active = app.AlarmList(arrayfun(@(a) a.State == "Active", app.AlarmList));
if isempty(active)
app.Banner.Text = 'No active alarms';
app.Banner.BackgroundColor = [0.86 0.86 0.86];
app.Banner.FontColor = [0.2 0.2 0.2];
return
end
% Highest severity wins on color; banner text lists all active.
sev = max([active.SeverityLevel]); % 3=Critical, 2=Warning, 1=Advisory
switch sev
case 3
app.Banner.BackgroundColor = [0.85 0 0]; % red
app.Banner.FontColor = [1 1 1];
case 2
app.Banner.BackgroundColor = [1 0.7 0]; % amber
app.Banner.FontColor = [0 0 0];
otherwise
app.Banner.BackgroundColor = [0.4 0.6 1.0]; % blue
app.Banner.FontColor = [1 1 1];
end
names = arrayfun(@(a) sprintf('%s=%.1f', a.Node, a.Value), active, ...
'UniformOutput', false);
app.Banner.Text = sprintf('ACTIVE (%d): %s', numel(active), strjoin(names, ' | '));
end
```
Note the `FontColor` assignment in **every** branch. That is not decoration. The banner's face
moves between saturated red, warning amber, comms blue and the neutral panel face, and the default
near-black text is barely readable on red at control-room distance. Set `FontColor` in the same
branch that sets `BackgroundColor`, never as a one-off at construction — see anti-pattern 30.
## Pattern C — Latched alarm with Acknowledge button
A latched alarm keeps the alarm state visible until the operator acknowledges it, even if the underlying value has returned to normal. This is the standard SCADA pattern (matches ISA-18.2).
**Latching and its Acknowledge control are one unit.** Latching without an ACK button leaves no
path back to normal — the banner holds its worst color for the rest of the session, which is worse
than not latching at all. If a design has no Acknowledge button, it must not latch: escalate while
the value is out of limits and clear when it returns (Pattern B). Wherever a hand-off document or
spec says "latched", it has to name the Acknowledge button too. See anti-pattern 31.
```matlab
properties (Access = private)
AlarmLatched (1,1) logical = false % is the alarm currently latched?
AlarmActive (1,1) logical = false % is the value currently above threshold?
end
```
In the data callback:
```matlab
function onTempChange(app, newValue)
if newValue >= app.HighCritical
app.AlarmActive = true;
app.AlarmLatched = true; % latch on rising edge
else
app.AlarmActive = false;
% Do NOT clear AlarmLatched here — only Acknowledge clears the latch.
end
refreshBanner(app);
refreshAckButton(app);
end
```
Acknowledge button callback:
```matlab
function onAcknowledge(app, ~, ~)
if ~app.AlarmActive
app.AlarmLatched = false;
end
% If still active, ack does nothing — operator must wait for value to clear.
refreshBanner(app);
refreshAckButton(app);
end
```
The Ack button should be enabled only when `AlarmLatched && ~AlarmActive` (alarm has cleared but is still latched).
## Anti-pattern: popups for live process alarms
**Never** use `uialert`, `uiconfirm`, or `msgbox` for a repeating process alarm condition. Anti-pattern #7 in the rules doc, also called out by ISA-18.2 (alarm fatigue). The popup fires every poll cycle, blocks the operator's view, and disappears once dismissed — exactly the opposite of what alarm visualization needs to do.
If a popup is unavoidable (e.g., the user explicitly insists), tame it:
- Fire **once on the rising edge**, not every tick.
- Use a non-blocking `CloseFcn`, not modal.
- Always pair with a persistent banner + source annotation, so the alarm survives the operator dismissing the popup.
## Pattern D — Minimal single-alarm screen
When the operator just needs notification on **one** condition (the simplest possible alarm HMI), the full Level-1/2/3 hierarchy is overkill. The minimal screen is: persistent banner, one gauge with `ScaleColors` band, one numeric readout, and an Acknowledge button. Use this layout for single-node monitoring tools, on-call alarm widgets, or test rigs.
```matlab
fig = uifigure('Name','Welder Temp Alarm', ...
'Color',[0.78 0.78 0.78], 'Theme','light');
gl = uigridlayout(fig,[3 2], ...
'RowHeight', {32, '1x', 40}, ...
'ColumnWidth', {'1x', 110}, ...
'BackgroundColor', [0.78 0.78 0.78], ...
'Padding', [10 10 10 10]);
% Row 1: banner across both columns
banner = uilabel(gl, 'Text','No active alarms', ...
'BackgroundColor',[0.86 0.86 0.86],'FontWeight','bold', ...
'HorizontalAlignment','center');
banner.Layout.Row = 1; banner.Layout.Column = [1 2];
% Row 2 col 1: gauge with alarm band at construction
g = uigauge(gl,'linear','Limits',[0 150]);
g.ScaleColors = [0.5 0.5 0.5; 1 0.7 0; 0.85 0 0];
g.ScaleColorLimits = [0 90; 90 100; 100 150];
g.Layout.Row = 2; g.Layout.Column = 1;
% Row 2 col 2: precise numeric readout
val = uieditfield(gl,'numeric','Editable','off', ...
'ValueDisplayFormat','%.1f °C', ...
'BackgroundColor',[0.86 0.86 0.86], ...
'HorizontalAlignment','right');
val.Layout.Row = 2; val.Layout.Column = 2;
% Row 3 col 2: Acknowledge button (enabled only when latched && cleared)
ackBtn = uibutton(gl,'Text','Acknowledge','Enable','off');
ackBtn.Layout.Row = 3; ackBtn.Layout.Column = 2;
```
## Cross-references
- Color palette and gray-field background: `references/color-and-layout-rules.md`
- Threshold lines on trend axes: `references/trend-config-reference.md`
- Connection-quality alarms (stale data, subscription lost): use Advisory severity (blue) — same banner mechanism
----
Copyright 2026 The MathWorks, Inc.
----
Related skills
| Skill | Stars | Updated | Works with | Status | Install |
|---|---|---|---|---|---|
| brainstormingobra/superpowersYou MUST use this before any creative work - creating features, building components, adding functionality, modifying behavior, or planning anything new, in software or out of it (a talk, a business, a renovation). | Stars: 322k | Updated | Claude CodeCodex | Verified | Install |
| brand-guidelinesanthropics/skillsApplies Anthropic's official brand colors and typography to any sort of artifact that may benefit from having Anthropic's look-and-feel. Use it when brand colors or style guidelines, visual formatting, or company design standards apply. | Stars: 198k | Updated | Claude CodeCodex | Verified | Install |
| frontend-designanthropics/skillsGuidance for distinctive, intentional visual design when building new UI or reshaping an existing one. Helps with aesthetic direction, typography, and making choices that don't read as templated defaults. | Stars: 198k | Updated | Claude CodeCodex | Verified | Install |
| mcp-builderanthropics/skillsGuide for creating high-quality MCP (Model Context Protocol) servers that enable LLMs to interact with external services through well-designed tools. Use when building MCP servers to integrate external APIs or services, whether in Python (FastMCP) or Node/TypeScript (MCP SDK). | Stars: 198k | Updated | Claude CodeCodex | Verified | Install |